Electrical Systems E-Line KAM Lighting Busbar Trunking System 25A...32A

Applications:
Warehouses / Workshops / Garages / Shopping Centres / All Industrial Buildings / Business Centres.
Specifications:
Flexible project solutions fast, easy and reliable to mount, up to 5 conductors / indicates the phase number on the tap-off plugs / a longer cable can be supplied with the tap-off boxes if required / very high mechanical strength / each 3m standard straight length is provided with 4 tap-off points at 75 cm distance / IP 54 protection degree is possible if required.
Electrical Systems E-Line KAP Plug-in Busbar Trunking System 40A...63A
Applications:
Workshops / Industrial Buildings / Business Centres.
Specifications:
The conductors are in electrolytic copper, tin plated and insulated along their full length with a self extinguishing plastic sleeve / fast, easy and reliable to mount / up to 5 conductors / indicates the phase with colored lid / to prevent to misuse the tap-off plugs and the tap-off boxes are designed in different sequences of conductors / the contacts for the conductors are silver plated copper to provide the best conductivity and resistance to corrosions. It also prevents the contacts to be over heated under possible overloads / Each 3m standard straight length is provided with 4 tap-off points at every 75cm / The protection degree is IP 55.
KAM and KAP Busbar Systems
KAM and KAP are busbar trunking systems for lighting (KAM) and small Power (KAP), designed and certified in full compliance with international standards IEC 439-1 and 2 and IEC 529. Both systems have been tested and certified at the CESI Institute in accordance with the full type test cycle stated in the relevant IEC codes.
General Characteristics
The housing is constructed in pregalvanised sheet metal which provides a substantial earth path. The housing gives to the line a very high mechanical strength, particularly suitable for industrial application. Applications in severe climatic conditions. The conductors are in electrolytic copper, tin plated and insulated along their Full length (except at tap off positions) with a self extinguishing plastic sleeve. 2 and 4 conductor versions are standard, with 3 or 5 conductor versions supplied upon request. Each 3m standard straight length is provided with 4 tap off points at 75 cm distance on one side of the trunking.
Joint
The joint is a fast locking type with a single screw. The joint contacts are silver plated and highly oversized in comparison with the nominal current to bear in total safety possible short term current peaks. The joint is further reinforced with tightening springs which ensures the the proper contact pressure between the conductors. The joint provides continuity of the housing when used as the earth conductor.
Feeder Units
Feeder units are available for installing at either end of the system or as a centre feed unit. The feeder units are IP55 as standard, and will accept supply cables up to ø16mm. The feeder units are supplied in kits including end closure and joint cover.
10A Tap Off Plugs (Only for KAM)
KAM 10B are single phase plugs, with fixed phase, without fuses, prewired with cable, cross section 3x1.5 mm2 and length 1m. They can be supplied with different length cable on request.
16A Tap Off Plugs
KAM 16K and KAP 16K are single phase plugs with fixed phase, available with or without fuse holders. A three phase version is also available, and can be used as a phase selectable unit for single phase operations. They can be wired with cables up to a maxi- mumof ø11mm.
32A Tap Off Boxes (Only For KAP)
KAP 32 are three-phase tap off boxes, available with fuse holder or with DIN rail to accept standard modular MCB's.
Tap Off Plugs
Tap off plugs are available in ratings from 10A to 32A. The plugs are manufactured in a self extinguishing material. The contacts for the phase and neutral conductors are silver plated copper to provide the best conductivity and resistance to corrosion. The tapping units for the KAM and KAP busbar systems have different plug-in configurations and are not interchangeable. All plugs are equipped with a separate earth contact and is the first to make and the last to break. The plugs have been tested at CESI Laboratories for 50 connection / disconnection duty cycles. The tapping units when plugged into the system provides both a good contact with the main conductors and a secure fixing of the plug on the housing.

|